Chiller Installation Requirements. 1. Foundation & Mounting ⇒ Concrete Plinth/Base: Should be flat, leveled, and minimum 150 mm above FFL. Designed to take dead load + dynamic load of the chiller. Ensure plinth length/width matches OEM mounting dimensions. ⇒ Vibration Isolators: Use spring isolators or neoprene pads below the chiller to reduce vibration and structure-borne noise. For rooftop units, include seismic restraints if required by local codes. 2. Piping Arrangements ⇒ Chilled Water Lines Inlet & Outlet properly labeled. Use flexible rubber bellows at inlet/outlet to absorb vibration and thermal expansion. Provide isolation valves, y-strainer, and flow switch. Install thermometers & pressure gauges at inlet and outlet for monitoring. Ensure correct pipe supports as per spacing schedule to avoid sagging. ⇒ Condenser Water Lines (for water-cooled only) Similar provisions as above. Ensure proper sloping and venting. Include chemical dosing point,...