Skip to main content

Chiller Installation Requirements

Chiller Installation Requirements.



1. Foundation & Mounting

⇒ Concrete Plinth/Base:

  • Should be flat, leveled, and minimum 150 mm above FFL. 
  • Designed to take dead load + dynamic load of the chiller.
  • Ensure plinth length/width matches OEM mounting dimensions.

⇒ Vibration Isolators:

  •  Use spring isolators or neoprene pads below the chiller to reduce vibration and structure-borne noise.
  • For rooftop units, include seismic restraints if required by local codes.
2. Piping Arrangements

⇒ Chilled Water Lines

  • Inlet & Outlet properly labeled.
  •  Use flexible rubber bellows at inlet/outlet to absorb vibration and thermal expansion.
  • Provide isolation valves, y-strainer, and flow switch.
  • Install thermometers & pressure gauges at inlet and outlet for monitoring.
  • Ensure correct pipe supports as per spacing schedule to avoid sagging.

⇒ Condenser Water Lines (for water-cooled only)

  • Similar provisions as above.
  •  Ensure proper sloping and venting.
  • Include chemical dosing point, bleed line, and auto bypass if needed.
3. Insulation

⇒ All chilled water pipes must be insulated with closed-cell elastomeric foam (min. 19 mm–25 mm). 

⇒ Properly sealed joints and vapor barrier to avoid condensation. 

⇒ For outdoor pipes: UV-resistant cladding (aluminum or PVC) to protect insulation.

 4. Air Clearance & Accessibility

⇒ Maintain manufacturer’s recommended service clearance:

  • Typically: 1.5–2.0 m on sides for maintenance.
  •  Overhead clearance for removing compressor/heat exchanger tube bundles.

⇒ Ensure safe access ladders, platforms, or walkways if rooftop-mounted.

 ⇒ No obstructions around air-cooled condensers — at least 1.5 m air clearance on all sides.

 ⚡ 5. Electrical Power Supply

⇒ Provide dedicated MCC/Panel for the chiller.

 ⇒ Size power cable, isolator, and breaker as per full-load amps + starting current.

⇒ Include:

  •  Remote start/stop
  • Earthing/Grounding
  • Cable tray support
  • Overload and short circuit protection

⇒ Power supply must be stable voltage (±5%) and have phase sequence monitor.

 6. Control & BMS Wiring :

⇒ Terminate low-voltage wiring for:

  • Remote start/stop
  • Chilled water pump interlock
  • Temperature and pressure sensors
  • Alarm signals and status

⇒ Use shielded cables and proper segregation from power lines.

⇒ Integrate with BMS (BACnet/MODBUS/IP) for monitoring and load optimization. 

 7. Drainage & Slope

⇒ Provide floor drain nearby.

 ⇒ Chiller base shall have slope and a drain line connection.

⇒ For water-cooled units: condenser blow-down or drain provision is mandatory.

8. Bypass & Flow Provisions

⇒ Primary loop should have:

  •  Motorized 2-way/3-way valve
  • Auto balancing valve or differential pressure controller

⇒ Ensure minimum flow rate is maintained through evaporator (use flow switch).

 ⇒ Install manual bypass during initial flushing/testing phase.

 

 9. Commissioning Readiness

⇒ All sensors (Temp, Pressure, Flow) shall be calibrated. 

⇒ Water quality testing done (pH, TDS, hardness). 

⇒ System flushed, cleaned, and passivated. 

⇒ Air venting and pressure testing of piping done. 

⇒ Dry run of pumps and chiller before full load testing.

 10. Tagging, Labeling & As-Built

⇒ Chiller model, capacity, refrigerant, and serial number plates must be visible. 

⇒ All piping and cabling labeled as per project specs. 

⇒ Provide as-built drawings, O&M manuals, and test reports post-installation.

Comments

Popular posts from this blog

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC common unit converter chart

 Here's a comprehensive HVAC unit converter chart: Volume Flow Rate 1.CFM (Cubic Feet per Minute) to CMH (Cubic Meters per Hour):  1 CFM ≈ 1.699 CMH 2.CFM to m³/s (Cubic Meters per Second):  1 CFM ≈ 0.000472 m³/s Airflow Velocity 1.FPM (Feet per Minute) to m/s (Meters per Second):  1 FPM ≈ 0.00508 m/s 2.m/s to FPM:  1 m/s ≈ 196.85 FPM Energy and Power 1.BTU/h (British Thermal Units per Hour) to kW (Kilowatts):  1 BTU/h ≈ 0.000293 kW 2.Tons of Refrigeration to kW:  1 Ton ≈ 3.517 kW Pressure 1.Inches of Water Gauge (in wg) to Pascals (Pa):  1 in wg ≈ 249.08 Pa 2.PSI (Pounds per Square Inch) to kPa (Kilopascals):  1 PSI ≈ 6.895 kPa Temperature 1.°F (Fahrenheit) to °C (Celsius):  °C = (°F - 32) × 5/9 2.°C to °F:  °F = °C × 9/5 + 32 Additional Conversions Length 1.Inches to Millimeters:   1 inch = 25.4 mm 2.Feet to Meters:  1 foot = 0.3048 meters Area Square Feet to Square Meters:  1 sq ft = 0.0929 sq m Volume Gallons to L...

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...