Skip to main content

Calculating Flow Rate

Calculating Flow Rate


To calculate the chilled water flow rate of a cooling coil (FCU/AHU), you need two parameters: q & ΔT.


Now, what's q?


q is the total heat load of a given room or space. It represents the sum total of internal & external heat loads.


In other words, the cooling coil needs to remove heat from the space at a rate of "q" in order to bring it to the desired temperature.


And who's carrying that q? It's the flowing chilled water, of course.


The other parameter, ΔT, is the temperature difference between the supply and return chilled water pipes. ΔT, as discussed earlier, is best used at 7-10 °C.


For example, if chilled water supply was at 5°C and the return is at 12°C, then your ΔT is 7°C.


The higher the delta T, the less the required water flow.

So, the question becomes:


How much water flow is needed to carry the total heat load, at a certain temperature rise?


How to calculate that flow:


q = Q*c*ΔT


Q: Flow rate of chilled water (L/s)


c: Heat capacity of water (kJ/L.°C, assumed constant at 4.184)


ΔT: Temperature rise between supply & return (usually 7-10°C, depends on system)


So,


Q = q / (c*ΔT)


Let's do an exercise:


A fan coil unit is supposed to cool a computer room having a total heat load of 100kW.


Determine the flow rate of chilled water required at AT of 8°C and at 10°C.

2 = q / (c*ΔT)


ΔT = 8°C,


Q = 100/(4.184*8) = 2.987~2.99 L/s


ΔΤ = 10°C, Q 100/(4.184*10) = 2.39008 ~ 2.39 L/s


You can see clearly how changing the AT can change flow rates, and consequently, pipe sizing, pump sizing, etc.


Aim to keep your equipment at a ΔT of 10°C to run a highly efficient system.


If you like reading more about the chilled water system, follow me. I'm posting about this complex system.



Comments

Popular posts from this blog

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC MEP Thumb Rules & Formulas (With Examples)

  HVAC MEP Thumb Rules & Formulas (With Examples) 1. Heat Load Calculation  Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft) Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25 2. CFM Calculation Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T) Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 3. AHU/FCU Sizing Rule: 1 TR = 400 CFM 2 TR Airflow = 800 CFM 4. Duct Sizing Velocity Limits: Main: 1400-1800 FPM 800 CFM @ 1000 FPM 0.8 sq.ft 14"x10" 5. Chilled Water Flow Rate Formula: GPM = BTU/hr / (500 x Delta T) Example: 24,000 BTU/hr GPM = 4.8 6. Pipe Sizing 1" pipe: 8-12 GPM 2" pipe: 30-40 GPM 35 GPM Use 2" 7. Chiller Sizing Formula: TR = BTU/hr / 12,000 Example: 60,000 BTU/hr → 5 TR 8. Cooling Tower Sizing Rule: Heat Rejection = 1.25 x Load 10 TR → Tower = 12.5 TR 9. Pump Head Calculation Formula: Power (kW) = (Q x H x 9.81) / (Efficiency x 1000) Example: Q = 5 L/s, H = 20 m, Efficiency = 0.75 Power 1.31 kW 10. Fresh Air Re...