Skip to main content

HVAC MEP Thumb Rules & Formulas (With Examples)

 HVAC MEP Thumb Rules & Formulas (With Examples)



1. Heat Load Calculation Formula:

Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft)

Example:

500 sq.ft office:

Q = 500 x 30 = 15,000 BTU/hr TR = 1.25


2. CFM Calculation Formula:

CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T)

Example:

12,000 BTU/hr, Delta T = 20°F CFM = 556


3. AHU/FCU Sizing Rule:

1 TR = 400 CFM

2 TR Airflow = 800 CFM


4. Duct Sizing Velocity Limits:

Main: 1400-1800 FPM

800 CFM @ 1000 FPM 0.8 sq.ft 14"x10"


5. Chilled Water Flow Rate Formula:

GPM = BTU/hr / (500 x Delta T)

Example:

24,000 BTU/hr GPM = 4.8


6. Pipe Sizing

1" pipe: 8-12 GPM

2" pipe: 30-40 GPM

35 GPM Use 2"


7. Chiller Sizing Formula:

TR = BTU/hr / 12,000

Example:

60,000 BTU/hr → 5 TR


8. Cooling Tower Sizing Rule:

Heat Rejection = 1.25 x Load

10 TR → Tower = 12.5 TR


9. Pump Head Calculation Formula:

Power (kW) = (Q x H x 9.81) / (Efficiency x 1000)

Example:

Q = 5 L/s, H = 20 m, Efficiency = 0.75

Power 1.31 kW


10. Fresh Air Requirement

Office: 15-20 CFM/person

300 CFM 20 people


11. Electrical Load

1 TR 1.25 kW

10 TR 12.5 kW


12. Condenser Water Flow

3 GPM per TR

15 TR 45 GPM


13. Return Air Duct

2 sq.in. per CFM

600 CFM 1200 sq.in. ≈ 10"x12"


14. VRV/VRF Capacity

1 HP = 0.8 TR

COP 3.5-4.5


15. Chilled Water Pipe Velocity

Chilled Water: 3-12 ft/s

Condenser: 6-9 ft/s

Comments

Popular posts from this blog

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC common unit converter chart

 Here's a comprehensive HVAC unit converter chart: Volume Flow Rate 1.CFM (Cubic Feet per Minute) to CMH (Cubic Meters per Hour):  1 CFM ≈ 1.699 CMH 2.CFM to m³/s (Cubic Meters per Second):  1 CFM ≈ 0.000472 m³/s Airflow Velocity 1.FPM (Feet per Minute) to m/s (Meters per Second):  1 FPM ≈ 0.00508 m/s 2.m/s to FPM:  1 m/s ≈ 196.85 FPM Energy and Power 1.BTU/h (British Thermal Units per Hour) to kW (Kilowatts):  1 BTU/h ≈ 0.000293 kW 2.Tons of Refrigeration to kW:  1 Ton ≈ 3.517 kW Pressure 1.Inches of Water Gauge (in wg) to Pascals (Pa):  1 in wg ≈ 249.08 Pa 2.PSI (Pounds per Square Inch) to kPa (Kilopascals):  1 PSI ≈ 6.895 kPa Temperature 1.°F (Fahrenheit) to °C (Celsius):  °C = (°F - 32) × 5/9 2.°C to °F:  °F = °C × 9/5 + 32 Additional Conversions Length 1.Inches to Millimeters:   1 inch = 25.4 mm 2.Feet to Meters:  1 foot = 0.3048 meters Area Square Feet to Square Meters:  1 sq ft = 0.0929 sq m Volume Gallons to L...

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...