Skip to main content

AHU Filter Selection and Calculation

AHU Filter Selection and Calculation


Understanding AHU Filter Selection in HVAC Systems Filters are critical components in an AHU because they remove dust particles and help maintain indoor air quality. Proper filter selection improves system performance, protects cooling coils, and reduces maintenance costs.


Common Filter Types in AHU:

  • Pre Filter - Removes larger particles (5-10 µm )
  • Fine Filter - Removes medium particles (1-5 μm )
  • HEPA Filter - Removes very fine particles for clean environments


Typical applications:

  • Office AHU → Pre + Fine Filter
  • Clean Room → Pre + Fine + HEPA
  • Pharmaceutical Area → Multi-stage filtration


Filter Area Calculation Formula:

Required Filter Area = Airflow ÷ Face Velocity

Example:

Airflow = 5000 CMH


Convert airflow:

5000÷3600 = 1.39 m³/s

Assume filter face velocity:

2.5 m/s

Filter Area:

1.39÷2.5

Required Filter Area = 0.56 m²

A=QVA=\frac{Q}{V}A=VQ


Where:

A = Filter area (m²)

Q = Airflow (m³/s)

V = Face velocity (m/s)


Recommended Face Velocity:

  • Pre Filter → 2.0-2.5 m/s
  • Fine Filter → 1.5-2.0 m/s
  • HEPA Filter → 0.45-0.6 m/s


Typical Pressure Drop:

  • Pre Filter → 30-60 Pa
  • Fine Filter → 70-150 Pa
  • HEPA Filter → 150-300 Pa


Correct filter selection helps achieve:

  • Better air quality
  • Lower fan energy consumption
  • Reduced maintenance frequency
  • Longer equipment life


Comments

Popular posts from this blog

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC MEP Thumb Rules & Formulas (With Examples)

  HVAC MEP Thumb Rules & Formulas (With Examples) 1. Heat Load Calculation  Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft) Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25 2. CFM Calculation Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T) Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 3. AHU/FCU Sizing Rule: 1 TR = 400 CFM 2 TR Airflow = 800 CFM 4. Duct Sizing Velocity Limits: Main: 1400-1800 FPM 800 CFM @ 1000 FPM 0.8 sq.ft 14"x10" 5. Chilled Water Flow Rate Formula: GPM = BTU/hr / (500 x Delta T) Example: 24,000 BTU/hr GPM = 4.8 6. Pipe Sizing 1" pipe: 8-12 GPM 2" pipe: 30-40 GPM 35 GPM Use 2" 7. Chiller Sizing Formula: TR = BTU/hr / 12,000 Example: 60,000 BTU/hr → 5 TR 8. Cooling Tower Sizing Rule: Heat Rejection = 1.25 x Load 10 TR → Tower = 12.5 TR 9. Pump Head Calculation Formula: Power (kW) = (Q x H x 9.81) / (Efficiency x 1000) Example: Q = 5 L/s, H = 20 m, Efficiency = 0.75 Power 1.31 kW 10. Fresh Air Re...