Skip to main content

Primary & Secondary Pumping Systems

Primary & Secondary Pumping Systems


As we all know, a system with only primary pumping at a constant volume will operate inefficiently for most of its lifetime.


The primary-secondary system solves one problem in the older system: high pumping energy consumption. But how does a primary-secondary system save pumping energy?


First, the system starts by separating the piping into two sides: production (primary) and distribution (secondary). The primary side contains the chillers and the primary pumps, while the secondary side contains the secondary pumps and the cooling units (FCU/AHU).


During times of partial load, which make more than 95 % of operational hours, the cooling coils won't be needing the same flow rate of chilled water because the heat load is less. This is controlled by a 2-way valve which regulates the flow of chilled water through the cooling coils based on the room's temperature.


To save costs and eliminate the need for bypass lines around cooling units, the secondary pumps contain a VSD (variable speed drive) that can regulate their operating point (flow, head) depending on the system's load.


But how does the pump's VSD know that the system's load has changed?

Using DPS.

Differential pressure sensors (DPS) are positioned at the end of each chilled water branch, measuring the difference in pressure between the supply and the return lines. The DPS sends a signal to the pumps' VSD to either increase or decrease the pumps' speed of rotation, and hence, the pumps' flow rate.


When the cooling load decreases, the 2-way valves restrict the flow to a certain degree, and the pressure difference between supply and return lines increases. The DPS can sense that change in pressure difference.


The opposite occurs when the load increases, demanding more flow. The 2-way valves open and the pressure difference drops, causing the DPS to send a signal to the pumps' VSD to slow down and decrease the pumps' flow rate.


Using variable-flow secondary pumping with constant-flow primary pumping allows for three things at once:


1. Maintain constant flow of chilled water through chillers ✔


2. Allow for a variable secondary pump's flow rate, and hence variable pump energy consumption, depending on the cooling load required


3. Select low-head primary pumps 



Comments

Popular posts from this blog

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC MEP Thumb Rules & Formulas (With Examples)

  HVAC MEP Thumb Rules & Formulas (With Examples) 1. Heat Load Calculation  Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft) Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25 2. CFM Calculation Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T) Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 3. AHU/FCU Sizing Rule: 1 TR = 400 CFM 2 TR Airflow = 800 CFM 4. Duct Sizing Velocity Limits: Main: 1400-1800 FPM 800 CFM @ 1000 FPM 0.8 sq.ft 14"x10" 5. Chilled Water Flow Rate Formula: GPM = BTU/hr / (500 x Delta T) Example: 24,000 BTU/hr GPM = 4.8 6. Pipe Sizing 1" pipe: 8-12 GPM 2" pipe: 30-40 GPM 35 GPM Use 2" 7. Chiller Sizing Formula: TR = BTU/hr / 12,000 Example: 60,000 BTU/hr → 5 TR 8. Cooling Tower Sizing Rule: Heat Rejection = 1.25 x Load 10 TR → Tower = 12.5 TR 9. Pump Head Calculation Formula: Power (kW) = (Q x H x 9.81) / (Efficiency x 1000) Example: Q = 5 L/s, H = 20 m, Efficiency = 0.75 Power 1.31 kW 10. Fresh Air Re...