Skip to main content

Understanding "Approach" in Chiller Systems: Causes, Impacts, and ASHRAE-Based Best Practices

Understanding "Approach" in Chiller Systems: Causes, Impacts, and ASHRAE-Based Best Practices


In chiller system performance, one critical parameter that is often overlooked but highly indicative of system health is the Approach Temperature.


What is Approach?

Approach refers to the temperature difference between:


Evaporator Approach: Leaving chilled water temperature vs. refrigerant evaporating temperature Condenser Approach: Leaving condenser water temperature vs. refrigerant condensing temperature


A low approach indicates efficient heat transfer, while a high approach signals performance degradation.


ASHRAE Guidance

What is a "Good" Approach?

Based on industry best practices and references from


ASHRAE:


Evaporator Approach (Typical Range):

  • 1-3°C (1.8-5.4°F) →Excellent / Clean condition
  • 3-5°C (5.4-9°F)  → Acceptable, monitor trend
  • > 5°C (9°F)  →Indicates fouling or performance issue

Condenser Approach (Typical Range):
  • 2-4°C (3.67.2°F) →Good performance
  • 4-6°C (7.2-10.8°F)  →Acceptable, needs observation
  • > 6°C (10.8°F) → Likely scaling, fouling, or airflow/water issue

Note: Values may vary depending on chiller type (air-cooled vs water-cooled), design conditions, and manufacturer specifications.

Always compare with commissioning baseline data.

Why Does High Approach Occur?
Several operational and maintenance related issues can increase approach values:
  • Fouling / Scaling on heat exchanger tubes
  • Poor water treatment leading to biofilm or deposits
  • Low water flow rate (pump issues, valve restrictions, airlocks)
  • Non-condensable gases in the refrigerant circuit (for condenser side)
  • Refrigerant issues (low charge, oil contamination)
  • Sensor inaccuracies or calibration drift Impact of High Approach
A rising approach is not just a number, it directly affects system efficiency and cost:
  • Reduced heat transfer efficiency
  • Increased compressor workload and energy consumption
  • Higher operating costs (kW/RT increases)
  • Potential for system trips under high load conditions
  • Shortened equipment lifespan
How to Handle High Approach

Proactive monitoring and corrective actions are essential:
⏩Regular tube cleaning (mechanical or chemical)
⏩Maintain proper water treatment program
⏩Verify design flow rates (check pumps, valves, strainers)
⏩Purge non-condensables from the system
⏩Check refrigerant charge and oil condition
⏩Calibrate temperature and pressure sensors periodically
⏩Trend approach values-early detection prevents major failures

Approach temperature is a simple yet powerful KPI in chiller systems.

Aligning your operation with ASHRAE recommended ranges ensures optimal efficiency, lower energy consumption, and longer equipment life.


Comments

Popular posts from this blog

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...

HVAC MEP Thumb Rules & Formulas (With Examples)

  HVAC MEP Thumb Rules & Formulas (With Examples) 1. Heat Load Calculation  Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft) Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25 2. CFM Calculation Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T) Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 3. AHU/FCU Sizing Rule: 1 TR = 400 CFM 2 TR Airflow = 800 CFM 4. Duct Sizing Velocity Limits: Main: 1400-1800 FPM 800 CFM @ 1000 FPM 0.8 sq.ft 14"x10" 5. Chilled Water Flow Rate Formula: GPM = BTU/hr / (500 x Delta T) Example: 24,000 BTU/hr GPM = 4.8 6. Pipe Sizing 1" pipe: 8-12 GPM 2" pipe: 30-40 GPM 35 GPM Use 2" 7. Chiller Sizing Formula: TR = BTU/hr / 12,000 Example: 60,000 BTU/hr → 5 TR 8. Cooling Tower Sizing Rule: Heat Rejection = 1.25 x Load 10 TR → Tower = 12.5 TR 9. Pump Head Calculation Formula: Power (kW) = (Q x H x 9.81) / (Efficiency x 1000) Example: Q = 5 L/s, H = 20 m, Efficiency = 0.75 Power 1.31 kW 10. Fresh Air Re...

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...