Skip to main content

How Do We Calculate Required Airflow in a Cleanroom?

How Do We Calculate Required Airflow in a Cleanroom?


In cleanroom engineering, airflow calculation is not a single-step process. It's a combination of multiple components that ensure cleanliness, pressurization, and system reliability.


Total Airflow = ACH Airflow + Fresh Air + Leakage +Heat Load Air (converted)


So how do engineers determine the right airflow?


Step 1. Air Changes per Hour (ACH) Method

This is the most widely used approach.

Airflow = ACH × Room Volume


Depending on the cleanroom classification:

ISO 5  ⏩240-600 ACH

ISO 6 ⏩ 90-180 ACH

ISO 7 ⏩ 30-60 ACH

ISO 8 ⏩ 10-25 ACH


This ensures that the air inside the room is replaced multiple times every hour to maintain cleanliness.


Step 2: Calculate Room Volume


Room size: 10m x 5m x 3m

Volume 150 m³


Step 3: Calculate ACH Airflow


Formula:

Airflow = Volume × ACH

ACH Airflow = 150 x 25 = 3750 CMH


Step 4: Add Fresh Air

Typically 10-20% or as per standard

Assume: 750 CMH


Step 5: Safety Margin (5%)

5% of 3750 = 187.5 CMH


Step 6: Add Leakage Airflow

  • Air lost through doors, gaps, and openings
  • Important for maintaining positive pressure

10% of 3750 = 375 CMH


Step 7: Heat Load → Convert to Airflow

QHeat = 1.2 × △ Theat Load × 3600

Assume: 

Heat Load = 5 kW (5000 W) 

△T = 10°C 

=1500 CMΗ


Step 8: Total Airflow

 Total Airflow = ACH Airflow + Fresh Air + Leakage + Heat Load Air 

Total Airflow =3750+750+187.5+375+1500=6562.5 CMH


Simple Understanding

  • ACH Airflow →Cleaning
  • Fresh Air→ People & oxygen
  • Leakage → Pressure control
  • Heat Load → Temperature control

Cleanroom airflow is not just calculation... it's about maintaining cleanliness all the time.



Comments

Popular posts from this blog

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...

HVAC MEP Thumb Rules & Formulas (With Examples)

  HVAC MEP Thumb Rules & Formulas (With Examples) 1. Heat Load Calculation  Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft) Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25 2. CFM Calculation Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T) Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 3. AHU/FCU Sizing Rule: 1 TR = 400 CFM 2 TR Airflow = 800 CFM 4. Duct Sizing Velocity Limits: Main: 1400-1800 FPM 800 CFM @ 1000 FPM 0.8 sq.ft 14"x10" 5. Chilled Water Flow Rate Formula: GPM = BTU/hr / (500 x Delta T) Example: 24,000 BTU/hr GPM = 4.8 6. Pipe Sizing 1" pipe: 8-12 GPM 2" pipe: 30-40 GPM 35 GPM Use 2" 7. Chiller Sizing Formula: TR = BTU/hr / 12,000 Example: 60,000 BTU/hr → 5 TR 8. Cooling Tower Sizing Rule: Heat Rejection = 1.25 x Load 10 TR → Tower = 12.5 TR 9. Pump Head Calculation Formula: Power (kW) = (Q x H x 9.81) / (Efficiency x 1000) Example: Q = 5 L/s, H = 20 m, Efficiency = 0.75 Power 1.31 kW 10. Fresh Air Re...

Understanding "Approach" in Chiller Systems: Causes, Impacts, and ASHRAE-Based Best Practices

Understanding "Approach" in Chiller Systems: Causes, Impacts, and ASHRAE-Based Best Practices In chiller system performance, one critical parameter that is often overlooked but highly indicative of system health is the Approach Temperature. What is Approach? Approach refers to the temperature difference between: Evaporator Approach: Leaving chilled water temperature vs. refrigerant evaporating temperature Condenser Approach: Leaving condenser water temperature vs. refrigerant condensing temperature A low approach indicates efficient heat transfer, while a high approach signals performance degradation. ASHRAE Guidance What is a "Good" Approach? Based on industry best practices and references from ASHRAE: Evaporator Approach (Typical Range): 1-3°C (1.8-5.4°F) →Excellent / Clean condition 3-5°C (5.4-9°F)  → Acceptable, monitor trend > 5°C (9°F)  →Indicates fouling or performance issue Condenser Approach (Typical Range): 2-4°C (3.67.2°F) →Good performance 4-6°C (7.2-...