HVAC Design for Clean Rooms - Hospitals & Pharma
HVAC Design for Clean Rooms - Hospitals & Pharma
1. Clean Room Classifications (ISO & GMP)
Classification Max. Particles ≥0.5µm / m³ Typical Use
ISO 5/ Class 100 3,520 OT, IV Room ISO 7/ Class 10,000 352,000 Compounding Area
ISO 8/ Class 100,000 3,520,000 Packing Area
2. Air Changes Per Hour (ACH)
Room Type Recommended ACH
Operation Theater (OT) 20-25
ICU/NICU 15-20
Cleanrooms ISO 7 60-90
Cleanrooms ISO 8 15-20
Example:
Room Volume = 5 m x 5 m x 3 m = 75 m³
ACH = 25 Airflow = (25 x 75)/60 = 31.25 CMM ≈ 1100 CFM
3. HEPA Filter Design
HEPA Efficiency: ≥99.97% @ 0.3µm
1 HEPA filter (24"x 24") handles ~500 CFM
OT needing 1000 CFM Use 2 filters
4. Room Pressure Differential
Area Type Pressure Difference
OT vs Corridor +10 to +15 Pa
ICU vs Corridor +5 to +10 Pa
Isolation Room -10 to-15 Pa
5. Laminar Airflow (LAF)
Velocity: 90 ± 20 ft/min (0.45 ± 0.05 m/s)
Area: ~9 ft x 6 ft above OT table
6. Humidity & Temperature Control
Area Temp (°C) RH (%)
OT 21-24 50-60
ICU / Patient Room 23-26 30-60
Pharma Clean room 20-22 45-55
7. Exhaust Systems
Negative pressure rooms require 100% exhaust
Use bag-in bag-out filters for hazardous exhausts
8. Validation Parameters
Air velocity test
Smoke pattern ( laminarity )
Particle count
HEPA integrity test
Example: Small OT Room (ISO 7 / GMP Grade B)
Parameter Value
Room Volume 6 m x 5 m x 3 m = 90 m³
ACH 25 Airflow = 1325 CFM
HEPA Filters 3 (500 CFM each)
Pressure +15 Pa
Temp/RH 22°C / 55%
Comments
Post a Comment