Skip to main content

HVAC Design for Clean Rooms - Hospitals & Pharma

 HVAC Design for Clean Rooms - Hospitals & Pharma



1. Clean Room Classifications (ISO & GMP) 

Classification Max. Particles ≥0.5µm / m³ Typical Use

ISO 5/ Class 100 3,520 OT, IV Room ISO 7/ Class 10,000 352,000 Compounding Area

ISO 8/ Class 100,000 3,520,000 Packing Area


2. Air Changes Per Hour (ACH)

Room Type Recommended ACH

Operation Theater (OT) 20-25

ICU/NICU 15-20

Cleanrooms ISO 7 60-90

Cleanrooms ISO 8 15-20

Example:

Room Volume = 5 m x 5 m x 3 m = 75 m³

ACH = 25 Airflow = (25 x 75)/60 = 31.25 CMM ≈ 1100 CFM


3. HEPA Filter Design

HEPA Efficiency: ≥99.97% @ 0.3µm

1 HEPA filter (24"x 24") handles ~500 CFM

OT needing 1000 CFM Use 2 filters


4. Room Pressure Differential

Area Type Pressure Difference

OT vs Corridor +10 to +15 Pa

ICU vs Corridor +5 to +10 Pa

Isolation Room -10 to-15 Pa


5. Laminar Airflow (LAF)

Velocity: 90 ± 20 ft/min (0.45 ± 0.05 m/s)

Area: ~9 ft x 6 ft above OT table


6. Humidity & Temperature Control

Area Temp (°C) RH (%)

OT 21-24 50-60

ICU / Patient Room 23-26 30-60

Pharma Clean room 20-22 45-55


7. Exhaust Systems

Negative pressure rooms require 100% exhaust

Use bag-in bag-out filters for hazardous exhausts


8. Validation Parameters

Air velocity test

Smoke pattern ( laminarity )

Particle count

HEPA integrity test

Example: Small OT Room (ISO 7 / GMP Grade B)

Parameter Value

Room Volume 6 m x 5 m x 3 m = 90 m³

ACH 25 Airflow = 1325 CFM

HEPA Filters 3 (500 CFM each)

Pressure +15 Pa

Temp/RH 22°C / 55%

Comments

Popular posts from this blog

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...

HVAC MEP Thumb Rules & Formulas (With Examples)

  HVAC MEP Thumb Rules & Formulas (With Examples) 1. Heat Load Calculation  Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft) Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25 2. CFM Calculation Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T) Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 3. AHU/FCU Sizing Rule: 1 TR = 400 CFM 2 TR Airflow = 800 CFM 4. Duct Sizing Velocity Limits: Main: 1400-1800 FPM 800 CFM @ 1000 FPM 0.8 sq.ft 14"x10" 5. Chilled Water Flow Rate Formula: GPM = BTU/hr / (500 x Delta T) Example: 24,000 BTU/hr GPM = 4.8 6. Pipe Sizing 1" pipe: 8-12 GPM 2" pipe: 30-40 GPM 35 GPM Use 2" 7. Chiller Sizing Formula: TR = BTU/hr / 12,000 Example: 60,000 BTU/hr → 5 TR 8. Cooling Tower Sizing Rule: Heat Rejection = 1.25 x Load 10 TR → Tower = 12.5 TR 9. Pump Head Calculation Formula: Power (kW) = (Q x H x 9.81) / (Efficiency x 1000) Example: Q = 5 L/s, H = 20 m, Efficiency = 0.75 Power 1.31 kW 10. Fresh Air Re...

Understanding "Approach" in Chiller Systems: Causes, Impacts, and ASHRAE-Based Best Practices

Understanding "Approach" in Chiller Systems: Causes, Impacts, and ASHRAE-Based Best Practices In chiller system performance, one critical parameter that is often overlooked but highly indicative of system health is the Approach Temperature. What is Approach? Approach refers to the temperature difference between: Evaporator Approach: Leaving chilled water temperature vs. refrigerant evaporating temperature Condenser Approach: Leaving condenser water temperature vs. refrigerant condensing temperature A low approach indicates efficient heat transfer, while a high approach signals performance degradation. ASHRAE Guidance What is a "Good" Approach? Based on industry best practices and references from ASHRAE: Evaporator Approach (Typical Range): 1-3°C (1.8-5.4°F) →Excellent / Clean condition 3-5°C (5.4-9°F)  → Acceptable, monitor trend > 5°C (9°F)  →Indicates fouling or performance issue Condenser Approach (Typical Range): 2-4°C (3.67.2°F) →Good performance 4-6°C (7.2-...