Skip to main content

HVAC Design for Clean Rooms - Hospitals & Pharma

 HVAC Design for Clean Rooms - Hospitals & Pharma



1. Clean Room Classifications (ISO & GMP) 

Classification Max. Particles ≥0.5µm / m³ Typical Use

ISO 5/ Class 100 3,520 OT, IV Room ISO 7/ Class 10,000 352,000 Compounding Area

ISO 8/ Class 100,000 3,520,000 Packing Area


2. Air Changes Per Hour (ACH)

Room Type Recommended ACH

Operation Theater (OT) 20-25

ICU/NICU 15-20

Cleanrooms ISO 7 60-90

Cleanrooms ISO 8 15-20

Example:

Room Volume = 5 m x 5 m x 3 m = 75 m³

ACH = 25 Airflow = (25 x 75)/60 = 31.25 CMM ≈ 1100 CFM


3. HEPA Filter Design

HEPA Efficiency: ≥99.97% @ 0.3µm

1 HEPA filter (24"x 24") handles ~500 CFM

OT needing 1000 CFM Use 2 filters


4. Room Pressure Differential

Area Type Pressure Difference

OT vs Corridor +10 to +15 Pa

ICU vs Corridor +5 to +10 Pa

Isolation Room -10 to-15 Pa


5. Laminar Airflow (LAF)

Velocity: 90 ± 20 ft/min (0.45 ± 0.05 m/s)

Area: ~9 ft x 6 ft above OT table


6. Humidity & Temperature Control

Area Temp (°C) RH (%)

OT 21-24 50-60

ICU / Patient Room 23-26 30-60

Pharma Clean room 20-22 45-55


7. Exhaust Systems

Negative pressure rooms require 100% exhaust

Use bag-in bag-out filters for hazardous exhausts


8. Validation Parameters

Air velocity test

Smoke pattern ( laminarity )

Particle count

HEPA integrity test

Example: Small OT Room (ISO 7 / GMP Grade B)

Parameter Value

Room Volume 6 m x 5 m x 3 m = 90 m³

ACH 25 Airflow = 1325 CFM

HEPA Filters 3 (500 CFM each)

Pressure +15 Pa

Temp/RH 22°C / 55%

Comments

Popular posts from this blog

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC common unit converter chart

 Here's a comprehensive HVAC unit converter chart: Volume Flow Rate 1.CFM (Cubic Feet per Minute) to CMH (Cubic Meters per Hour):  1 CFM ≈ 1.699 CMH 2.CFM to m³/s (Cubic Meters per Second):  1 CFM ≈ 0.000472 m³/s Airflow Velocity 1.FPM (Feet per Minute) to m/s (Meters per Second):  1 FPM ≈ 0.00508 m/s 2.m/s to FPM:  1 m/s ≈ 196.85 FPM Energy and Power 1.BTU/h (British Thermal Units per Hour) to kW (Kilowatts):  1 BTU/h ≈ 0.000293 kW 2.Tons of Refrigeration to kW:  1 Ton ≈ 3.517 kW Pressure 1.Inches of Water Gauge (in wg) to Pascals (Pa):  1 in wg ≈ 249.08 Pa 2.PSI (Pounds per Square Inch) to kPa (Kilopascals):  1 PSI ≈ 6.895 kPa Temperature 1.°F (Fahrenheit) to °C (Celsius):  °C = (°F - 32) × 5/9 2.°C to °F:  °F = °C × 9/5 + 32 Additional Conversions Length 1.Inches to Millimeters:   1 inch = 25.4 mm 2.Feet to Meters:  1 foot = 0.3048 meters Area Square Feet to Square Meters:  1 sq ft = 0.0929 sq m Volume Gallons to L...

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...