CHILLER CONTROL PARAMETERS
CHILLER CONTROL PARAMETERS
1.Chilled Water Supply Temperature (CHW Supply Temp)
⇒ Setpoint usually 6–7°C.
⇒ Maintained by controlling compressor operation and refrigerant flow.
⇒ Impacts building cooling efficiency directly.
2.Chilled Water Return Temperature (CHW Return Temp)
⇒ Normally around 12–14°C from building side.
⇒ Indicates cooling load — higher return temp = higher demand.
3.Delta T (Temp Difference)
⇒ CHW Return – CHW Supply. Ideal: 6–8°C.
⇒ Lower delta T = flow too high or load too low.
⇒ Important for energy optimization and sizing.
4.Chilled Water Flow Rate
⇒ Must meet minimum flow for evaporator (to avoid freezing).
⇒ Controlled by VFD pumps, 2-way valves, or bypass lines.
⇒ Flow switch protects evaporator from dry run.
5.Evaporator Pressure & Temperature
⇒ Used to monitor refrigerant evaporation process.
⇒ Sudden drop = low refrigerant or blocked flow.
⇒ Used to trip chiller on low pressure.
6.Condenser Water Temperature (In/Out) (Water-Cooled only)
⇒ Typical: 30–37°C in / 35–42°C out.
⇒ Affects condenser pressure and overall chiller efficiency.
⇒ High condenser temp = poor cooling tower performance.
7.Refrigerant Pressure – Low Side & High Side
⇒ Low side (evaporator): for cooling.
⇒ High side (condenser): for heat rejection.
⇒ Helps detect abnormal conditions like:
- Low refrigerant charge
- Blockage
- Overheating
⇒ Shows actual compressor load.
⇒ High current = heavy load or high head pressure.
⇒ Used for overload protection and energy monitoring.
9.Alarms & Trips
⇒ Low CHW flow
⇒ High condenser pressure
⇒ Low refrigerant pressure
⇒ Compressor overload
⇒ Sensor failure
10.BMS/PLC Integration Points
⇒ Start/Stop command
⇒ CHW temp setpoint override
⇒ Status feedback (Running/Fault)
⇒ Real-time monitoring of: Temps, Pressures, Flow, Alarms.
Comments
Post a Comment