Skip to main content

CHILLER CONTROL PARAMETERS

CHILLER CONTROL PARAMETERS



1.Chilled Water Supply Temperature (CHW Supply Temp)

⇒ Setpoint usually 6–7°C. 

⇒ Maintained by controlling compressor operation and refrigerant flow. 

⇒ Impacts building cooling efficiency directly.


2.Chilled Water Return Temperature (CHW Return Temp) 

⇒ Normally around 12–14°C from building side. 

⇒ Indicates cooling load — higher return temp = higher demand.


3.Delta T (Temp Difference) 

⇒ CHW Return – CHW Supply. Ideal: 6–8°C. 

⇒ Lower delta T = flow too high or load too low. 

⇒ Important for energy optimization and sizing.


4.Chilled Water Flow Rate 

⇒ Must meet minimum flow for evaporator (to avoid freezing). 

⇒ Controlled by VFD pumps, 2-way valves, or bypass lines. 

⇒ Flow switch protects evaporator from dry run.


5.Evaporator Pressure & Temperature 

⇒ Used to monitor refrigerant evaporation process. 

⇒ Sudden drop = low refrigerant or blocked flow. 

⇒ Used to trip chiller on low pressure.


6.Condenser Water Temperature (In/Out) (Water-Cooled only) 

⇒ Typical: 30–37°C in / 35–42°C out. 

⇒ Affects condenser pressure and overall chiller efficiency. 

⇒ High condenser temp = poor cooling tower performance.


7.Refrigerant Pressure – Low Side & High Side 

⇒ Low side (evaporator): for cooling. 

⇒ High side (condenser): for heat rejection. 

⇒ Helps detect abnormal conditions like: 

  • Low refrigerant charge  
  • Blockage  
  • Overheating


8.Compressor Current (Amps)
 

⇒ Shows actual compressor load. 

⇒ High current = heavy load or high head pressure. 

⇒ Used for overload protection and energy monitoring.


9.Alarms & Trips 

⇒ Low CHW flow 

⇒ High condenser pressure 

⇒ Low refrigerant pressure 

⇒ Compressor overload 

⇒ Sensor failure


10.BMS/PLC Integration Points 

⇒ Start/Stop command 

⇒ CHW temp setpoint override 

⇒ Status feedback (Running/Fault) 

⇒ Real-time monitoring of: Temps, Pressures, Flow, Alarms.

Comments

Popular posts from this blog

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...

HVAC MEP Thumb Rules & Formulas (With Examples)

  HVAC MEP Thumb Rules & Formulas (With Examples) 1. Heat Load Calculation  Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft) Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25 2. CFM Calculation Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T) Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 3. AHU/FCU Sizing Rule: 1 TR = 400 CFM 2 TR Airflow = 800 CFM 4. Duct Sizing Velocity Limits: Main: 1400-1800 FPM 800 CFM @ 1000 FPM 0.8 sq.ft 14"x10" 5. Chilled Water Flow Rate Formula: GPM = BTU/hr / (500 x Delta T) Example: 24,000 BTU/hr GPM = 4.8 6. Pipe Sizing 1" pipe: 8-12 GPM 2" pipe: 30-40 GPM 35 GPM Use 2" 7. Chiller Sizing Formula: TR = BTU/hr / 12,000 Example: 60,000 BTU/hr → 5 TR 8. Cooling Tower Sizing Rule: Heat Rejection = 1.25 x Load 10 TR → Tower = 12.5 TR 9. Pump Head Calculation Formula: Power (kW) = (Q x H x 9.81) / (Efficiency x 1000) Example: Q = 5 L/s, H = 20 m, Efficiency = 0.75 Power 1.31 kW 10. Fresh Air Re...

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...