Skip to main content

CHILLER CONTROL PARAMETERS

CHILLER CONTROL PARAMETERS



1.Chilled Water Supply Temperature (CHW Supply Temp)

⇒ Setpoint usually 6–7°C. 

⇒ Maintained by controlling compressor operation and refrigerant flow. 

⇒ Impacts building cooling efficiency directly.


2.Chilled Water Return Temperature (CHW Return Temp) 

⇒ Normally around 12–14°C from building side. 

⇒ Indicates cooling load — higher return temp = higher demand.


3.Delta T (Temp Difference) 

⇒ CHW Return – CHW Supply. Ideal: 6–8°C. 

⇒ Lower delta T = flow too high or load too low. 

⇒ Important for energy optimization and sizing.


4.Chilled Water Flow Rate 

⇒ Must meet minimum flow for evaporator (to avoid freezing). 

⇒ Controlled by VFD pumps, 2-way valves, or bypass lines. 

⇒ Flow switch protects evaporator from dry run.


5.Evaporator Pressure & Temperature 

⇒ Used to monitor refrigerant evaporation process. 

⇒ Sudden drop = low refrigerant or blocked flow. 

⇒ Used to trip chiller on low pressure.


6.Condenser Water Temperature (In/Out) (Water-Cooled only) 

⇒ Typical: 30–37°C in / 35–42°C out. 

⇒ Affects condenser pressure and overall chiller efficiency. 

⇒ High condenser temp = poor cooling tower performance.


7.Refrigerant Pressure – Low Side & High Side 

⇒ Low side (evaporator): for cooling. 

⇒ High side (condenser): for heat rejection. 

⇒ Helps detect abnormal conditions like: 

  • Low refrigerant charge  
  • Blockage  
  • Overheating


8.Compressor Current (Amps)
 

⇒ Shows actual compressor load. 

⇒ High current = heavy load or high head pressure. 

⇒ Used for overload protection and energy monitoring.


9.Alarms & Trips 

⇒ Low CHW flow 

⇒ High condenser pressure 

⇒ Low refrigerant pressure 

⇒ Compressor overload 

⇒ Sensor failure


10.BMS/PLC Integration Points 

⇒ Start/Stop command 

⇒ CHW temp setpoint override 

⇒ Status feedback (Running/Fault) 

⇒ Real-time monitoring of: Temps, Pressures, Flow, Alarms.

Comments

Popular posts from this blog

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC common unit converter chart

 Here's a comprehensive HVAC unit converter chart: Volume Flow Rate 1.CFM (Cubic Feet per Minute) to CMH (Cubic Meters per Hour):  1 CFM ≈ 1.699 CMH 2.CFM to m³/s (Cubic Meters per Second):  1 CFM ≈ 0.000472 m³/s Airflow Velocity 1.FPM (Feet per Minute) to m/s (Meters per Second):  1 FPM ≈ 0.00508 m/s 2.m/s to FPM:  1 m/s ≈ 196.85 FPM Energy and Power 1.BTU/h (British Thermal Units per Hour) to kW (Kilowatts):  1 BTU/h ≈ 0.000293 kW 2.Tons of Refrigeration to kW:  1 Ton ≈ 3.517 kW Pressure 1.Inches of Water Gauge (in wg) to Pascals (Pa):  1 in wg ≈ 249.08 Pa 2.PSI (Pounds per Square Inch) to kPa (Kilopascals):  1 PSI ≈ 6.895 kPa Temperature 1.°F (Fahrenheit) to °C (Celsius):  °C = (°F - 32) × 5/9 2.°C to °F:  °F = °C × 9/5 + 32 Additional Conversions Length 1.Inches to Millimeters:   1 inch = 25.4 mm 2.Feet to Meters:  1 foot = 0.3048 meters Area Square Feet to Square Meters:  1 sq ft = 0.0929 sq m Volume Gallons to L...

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...