Skip to main content

VRF:- Variable Refrigerant Flow

 VRF:- Variable Refrigerant Flow


What is Variable Refrigerant Flow?


The term “Variable Refrigerant Flow refers to the capability of a HVAC system to control the amount of refrigerant flowing to each of the indoor units/evaporators, enabling the use of multiple evaporators of differing capacities and configurations, individualized comfort control, simultaneous heating and cooling in different zones with heat recovery from one zone to another”


Variable Refrigerant Flow (VRF) System is an engineered direct expansion (DX) multi-split system incorporating at least one variable capacity compressor distributing refrigerant through a piping network to multiple indoor fan coil units each capable of individual zone temperature control, through a zone temperature control devices and common communications network. Variable refrigerant flow implies three or more steps of control on common, inter-connecting piping.


Why do we use VRF Systems?


• Decentralized System – Zone Comfort

• Efficiency – Pay for what you use

• Flexible

• Simple to design

• Easy to install and commission

• Good value


Indoor Unit Capacity Control


• Indoor units individually controlled by LEV

• LEV has 2 functions Control the superheat across indoor unit evaporator Acts as solenoid valve to stop refrigerant flow to indoor units that are off


Smart Indoor Coil Design


• If superheat is high

the valve will open

• If Superheat is low

the valve will close


Outdoor Unit Capacity Control


• Compressor speed is controlled by

a VFD based on common

saturated suction temperature

and capacity required

• Refrigerant volume flow is directly

proportional to the compressor

speed

• Power input is directly

proportional to the cube of the

compressor speed


Different VRF Systems


• 2 Pipe System cooling only

• 2 Pipe System heat pump cooling or heating

• 3 Pipe System simultaneous cooling and

heating

• 2 Pipe System simultaneous cooling and

heating – air cooled

• 2 Pipe System simultaneous cooling and

heating – water and geothermal application


DIVERSITY


1. Time of Day

     VRF System can heat and cool simultaneously

2. Heating & Cooling

     VRF System can efficiently distribute 

cooling capacity to keep up with changing 

solar loads

3. Occupancy

      As people move throughout a building, VRF System can move energy around to maintain comfort levels within setpoint


VRF Indoor Unit Overview


• 1,2 & 4 Way Cassette

• Ducted horizontal

• Ducted

 vertical

• Ceiling Suspended

• Wall Mounted

• Floor Standing

• Water heating

   modules



Comments

Popular posts from this blog

Type of Heat Exchanger

 There are several types of heat exchangers used in HVAC systems, including: 1. Coil Type:     - Chilled water coils     - Hot water coils     - DX (direct expansion) coils     - Evaporator coils     - Condenser coils 2. Shell and Tube Type:     - U-tube heat exchangers     - Straight tube heat exchangers 3. Plate Type:     - Plate and frame heat exchangers     - Plate and shell heat exchangers 4. Finned Tube Type:     - Finned tube heat exchangers 5. Spiral Type:     - Spiral heat exchangers 6. Regenerative Type:     - Regenerative heat exchangers 7. Adiabatic Type:     - Adiabatic wheel heat exchangers 8. Run-Around Coil Type:     - Run-around coil heat exchangers These heat exchangers are used in various applications, including: - Air conditioning - Heating - Ventilation - Refrigeration - Heat recovery - Industrial processes Each type of hea...

HVAC common unit converter chart

 Here's a comprehensive HVAC unit converter chart: Volume Flow Rate 1.CFM (Cubic Feet per Minute) to CMH (Cubic Meters per Hour):  1 CFM ≈ 1.699 CMH 2.CFM to m³/s (Cubic Meters per Second):  1 CFM ≈ 0.000472 m³/s Airflow Velocity 1.FPM (Feet per Minute) to m/s (Meters per Second):  1 FPM ≈ 0.00508 m/s 2.m/s to FPM:  1 m/s ≈ 196.85 FPM Energy and Power 1.BTU/h (British Thermal Units per Hour) to kW (Kilowatts):  1 BTU/h ≈ 0.000293 kW 2.Tons of Refrigeration to kW:  1 Ton ≈ 3.517 kW Pressure 1.Inches of Water Gauge (in wg) to Pascals (Pa):  1 in wg ≈ 249.08 Pa 2.PSI (Pounds per Square Inch) to kPa (Kilopascals):  1 PSI ≈ 6.895 kPa Temperature 1.°F (Fahrenheit) to °C (Celsius):  °C = (°F - 32) × 5/9 2.°C to °F:  °F = °C × 9/5 + 32 Additional Conversions Length 1.Inches to Millimeters:   1 inch = 25.4 mm 2.Feet to Meters:  1 foot = 0.3048 meters Area Square Feet to Square Meters:  1 sq ft = 0.0929 sq m Volume Gallons to L...

VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE

  VALVES USED IN A CHILLER SYSTEM AND THE TYPICAL VALVE PACKAGE 1.Chilled Water Side Valves ⇒Isolation valve (manual/electric actuated). ⇒ Installed on CHW supply and return lines.  ⇒ Used to isolate chiller for maintenance. 2. Balancing Valve (Manual or Automatic)  ⇒ Ensures correct flow rate to/from chiller.  ⇒ Helps maintain Delta T and proper flow distribution.  ⇒ Located after evaporator outlet (return line). 3. Differential Pressure Bypass Valve (if 2-way valves in system)  ⇒ Prevents excess pressure build-up when terminals shut.  ⇒ Maintains flow through chiller. 4. Flow Switch  ⇒ Senses chilled water flow across evaporator.  ⇒ Safety interlock: trips chiller if flow is lost.  ⇒ Usually paddle type or electronic. 5. Air Vent Valve (Manual or Automatic)  ⇒ Removes air pockets.  ⇒ Placed at high points of piping and chiller headers. 6. Drain Valve  ⇒ For flushing, cleaning, and maintenance.  ⇒ Located at low poin...